Product Description

Detect main insulation faults of power cables of voltage class 35kV and below; calibrate cable length; accurately detect cable burial direction and depth.

II. Configuration

 

Cable fault location system

Name

Model

QTY

TDR

HZ-501B

1

Pinpionter

Cable route tracer

HZ-503

HZ-504

1

High voltage generator

HZ-535-4

1

 

III.Main Technical data

1) Low-voltage pulse, high-voltage flashover method, audio method, acousto-magnetic synchronization method, electromagnetic induction method, DC impact

2) Test range: test distance: 60km, detection depth: 2-5m;

3) Impact high voltage: 0~35KV  optional

4) Short circuit current: 0 ~ 320mA

5) Burn through power: 0 ~ 2450J

IV The introduction of every part

1,TDR  HZ-501B

 Main technical parameters

1)Industrial grade 5 inch LCD display, key board operation.-

2)With distance, speed and resistance measurement function.

3)Automatic continuous sampling and never lose any discharge waveform.

4)Testing method: flashover sampling, low-impulse method.

5)Measure distance: Smax:60kmSmin:15m.

6) Pre-locating accuracy: absolute  10m ; relative: 1%

7) Built-in DC power 2.6V/10.4Ah, also connect with external AC 220V 50Hz power supply

2 PinpointerHZ-503

Usage: Cable fault pointing device is to determine the power cable failure point by means of acoustics. An electronic flashover is generated by means of an impingement discharge generator. The acoustic and magnetic signals of the electronic flashover wave are picked up and amplified by the corresponding probes, and are judged by hearing and visual. To determine the exact location of the fault point, that is, to complete the precise positioning task within the rough measurement range of the cable fault point.

Performance:

(1) Acoustic waves and electromagnetic waves generated when the fault point is discharged can be synchronously received to determine the position of the cable fault point.

(2) Magnification, 500,000 times.

(3) Working voltage: 9V20%

(4) Quiescent current: <10mA

(5) Receive signal: vibration and magnetic field signals when the fault is discharged

(6) Output impedance: 350

(7) Positioning accuracy: 0.2m

3.Cable route tracer HZ-504

UsageCable path meter is a special instrument for accurately detecting the position and depth of buried cable in a certain range; path detection is completed by the path signal generator and path signal receiver (cable fault fixed point meter); The cooperation between the two uses the operation to accurately locate the cable path within the approximate cable embedding range.

Main composition

Path detection is mainly composed of path signal generator and receiver

index parameter

a) Working mode: continue square wave signal

b) Output signal: audio

c) Receive signal: audio

d) output power: 100W;

f) Working power supply: 220V (110%) 50Hz (15%);

4 High voltage generator  HZ-535-4

1) the main performance characteristics:

With over-current, over-voltage, over-heat automatic protection function;

 Uniform and controllable high-voltage pulse output;

 Super short-circuit protection function, which can make the high-voltage output directly short-circuit to the ground;

 It has dual 1.5-level pointer meter display for current and voltage, which is intuitive and clear, and the impact discharge process is clear at a glance;

 High-voltage side voltage measurement, real-time and accurate;

 With zero start protection, and potentiometer zero output function, safe and reliable;

 Unique high-voltage measurement design, in the stopped state, the voltmeter can indicate the capacitor voltage in real time;

 It has an emergency stop function, which can cut off the high voltage output in an emergency;

Main technical indicators:

Impact high voltage: 0~35kV optional

High voltage divider: voltage accuracy level 1.5

Built-in capacitance: 4F

Discharge power: 0-2450J Charge current: 320mA

Output voltage polarity: negative polarity

Impact power: 400W

Overcurrent protection: 16A (more than 3 seconds)

Over temperature protection: 85C

Volume: 430L345W545H

Weight: not more than 40kg

Working power supply: AC 220V10%/50Hz2Hz

Ambient temperature: -20~+60    